Technical characteristics of insulation
(supplied on flanged models only)
Internal part
- Material: rigid closed cell expanded polyurethane foam
- Thickness: 2.3/8" (60 mm)
- Density: 3 lb/ft
3
(45 kg/m
3
)
- Thermal conductivity (ISO 2581): 0.16 BTU/in (0.023 W/mK)
- Temperature range: 32-220°F (0÷105°C)
External cover
- Material: embossed aluminium
- Thickness: 7.0-mil (0,7 mm)
- Fire resistance (DIN 4102): Class 1
Head covers
- Heat moulded material: PS
Operating principle
When a single system contains a primary production circuit, with its
own pump, and a secondary user circuit, with one or more
distribution pumps, operating conditions may arise in the system
whereby the pumps interact, creating abnormal variations in circuit
flow rates and pressures.
The hydronic separator creates a zone with a low pressure loss,
which enables the primary and secondary circuits connected to it to
be hydronically independent of each other; the flow in one circuit
does not create a flow in the other if the pressure loss in the
common section is negligible.
In this case, the flow rate in the respective circuits depends
exclusively on the flow rate characteristics of the pumps, preventing
reciprocal influence caused by connection in series.
Therefore, using a device with these characteristics means that the
flow in the secondary circuit only circulates when the relevant pump
is on, permitting the system to meet the specific load requirements
at that time. When the secondary pump is off, there is no circulation
in the secondary circuit; the whole flow rate produced by the
primary pump is by-passed through the separator.
With the hydronic separator, it is thus possible to have a production
circuit with a constant flow rate and a distribution circuit with a
variable flow rate; these operating conditions are typical of modern
heating and air-conditioning systems.
Three possible hydronic balance situations are shown below.
Dimensions
Gprimary = Gsecondary Gprimary > Gsecondary
Gprimary < Gsecondary
Primary Secondary
Gp Gs
Primary Secondary
Gp Gs
Primary Secondary
Gp Gs
Gp Gs
primariy
circuit
secondary
circuit
A
2”
2
1/2
3”
4”
B
11/4"
1
1/4"
1
1/4"
1
1/4"
C
13”
13”
18”
18”
D
91/2"
9
1/2"
15"
15"
E
15 1/2
15
1/2
17"
17"
F
14”
14”
18”
18”
F
B
D C E
AA
A
1"
1 1/4
1
1/2
D EC
B
AA
B
8
7/8
9
3/4
11
1/8
C
7 5/8
8
7/8
9
1/4
D
6 5/8
9
1/2
10
1/4
E
8”
8
1/2
8
7/8
Code
548050/2A
548060/2A
548080/2A
548100/2A
Code
548006A
548007A
548008A
Tmax 230°F
P
max150 psi
T
max 220°F
P
max150 psi
Hydro Separator
Series 548
Tmax 230°F
P
max150 psi
T
max 220°F
P
max150 psi
Weight (lb)
7.5
8.3
12.5
Weight (lb)
73
79
108
117
Size
Volume (gal)
1”
0.5
1 1/4”
0.7
1 1/2”
1.3
DN 50
4
DN 65
4
DN 80
8
DN 100
8
Hydro Separator
Series 548
51